What To Do When Level-2 Messages Are Displayed - Kidde ARIES Installation, Operation And Maintenance Manual

Fire alarm/suppression
Table of Contents

Advertisement

Device Address 010
3-2.5.8.6
Figure 3-31. Typical Display When Manually Scrolling Through Level-2 Events
P/N 06-236530-001
Alarm Indication
010
ALARM ON
DIS 00
CNTDN 00
No. of Extinguishing-System Releases
Figure 3-30. Typical Multiple Level-2 Event-Type Display
You may manually scroll the display among the active Level-2 events and
completed Level-1 events by using the <SCROLL> Key.

What to Do When Level-2 Messages are Displayed

Press the <SCROLL> Key to display the information for the highest-priority
and subsequent events. The display will show 1st event or "More than 64
Alarms" when all of current Level-2 and completed Level-1 events have
been manually displayed. The upper line of the display will revert to
showing the highest-priority event approximately 5 seconds after the last
press of the <SCROLL> Key. You may then manually scroll the display
among the active Level-2 and completed Level-1 events.
The appearance of the display when manually scrolling through the active
Level-2 events is shown in Figure 3-31.
Device Address 010
010 ALARM
COMPUTER ROOM
Device-Specific
Custom Message
Device Type Reporting Alarm
PHOTOELECTRIC
ABT 01
ALM 02
PAS 00
No. of Alarms
No. of Activated Abort Stations
No. of Countdowns to Release in Progress
Alarm Indication
Device Type Reporting Alarm
ON
MANUAL STATION
3-115
No. of PAS Countdowns
in Progress
August 2013