3-2.5.2.5.12 How to Activate Control Modules (i.e., as AO, ASM or RRM)
There is no indication at the control unit that an output is activated. Be sure to
de-activate the output after proper operation has been confirmed.
Ensure that the control modules are not activating suppression systems or
controlling critical facility operations such as computer power. Physically
disconnect the wiring to all agent-release and pre-action-sprinkler circuits and
CAUTION
bypass all affected power-off circuits before activating any control modules if
the control modules are activating suppression systems or are shutting off
power. Restore the system to normal operating condition at the conclusion of
all control-module activations and any other functional tests.
Step
1
Press 0 Key
2
Enter Password; press "Enter" Key
3
Press 4 Key
4
Press "Scroll" Key
5
Press 7 Key
6
Press "Scroll" Key twice
7
Press 8 Key
8
Press 1 Key and then press "Enter" Key
9
Enter starting SLC address and ending SLC
address.
Use XXX format for addresses.
Press "Enter" Key to confirm address range of
control modules to activate.
10
Return to Step 8 and make another selection
(optional)
11
De-activate all control modules after confirming
proper operation
12
Press "Backspace" Key (as required)
3-2.5.2.5.13 How to De-Activate Control Modules (i.e., AO or ASM)
August 2013
Purpose: To manually activate one or more control modules during
system testing to confirm the proper operation of control functions via
AOs, NAC operation via ASMs or RRMs.
Note: All control modules must be manually de-activated via a menu
operation or a system reset before the system can be returned
to normal operating condition.
Action
Purpose: To manually de-activate one or more control modules that
were activated during system testing.
Note: Each control module must be manually de-activated via this
menu operation or a system reset before the system can be
returned to normal operating condition.
3-90
Result
Initiate Menu Access
Gain access to menus
Enter Test-Menu branch
Access additional Test-Menu options
Select "Output Test" option
Access additional Outputs-Test options
Select "SLC Outputs"
Specify range of control modules and activate.
Activate additional control modules
See Paragraph 3-2.5.2.5.14
Exit Menu System