Kidde ARIES Installation, Operation And Maintenance Manual page 137

Fire alarm/suppression
Table of Contents

Advertisement

Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 3 Key
4
Press "Scroll" Key
5
Press 4 Key
6
Press "Scroll" Key
7
Press 4 Key
8
Wait until "Configuring Basic Suppression System
and Initializing Configuration" messages
disappear from the display.
3-2.5.2.4.29 How to Activate Alarm Verification for Smoke Detectors
Step
1
Press 0 Key
2
Enter Password; Press "Enter" Key
3
Press 3 Key
4
Press "Scroll" Key
5
Press 4 Key
6
Press "Scroll" Key
7
Press 5 Key
8
Press 1 Key and then press "Enter" Key to confirm
selection.
9
Use keypad to enter single address or range of
smoke-detector addresses to be verified.
Press "Enter" Key to confirm selection.
10
Press "Backspace" Key (as required)
11
Wait until "Initializing Configuration" message
disappears from the display.
P/N 06-236530-001
Note: Wait for each SLC device to report a "Not-Registered" trouble
message and ensure that all these trouble messages have been
acknowledged
Procedure.
Action
Purpose: To activate alarm-verification for one or more smoke
detectors. Refer to Paragraph 3-2.5.5.3.
Action
3-55
before
proceeding
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access additional options
Select "Programming"
Access additional options
Activate "AutoSetup"
Exit Menu System and Resume Normal
Operations.
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access additional options
Select Programming option
Access additional options
Select "Alarm-Verification" option
Activate alarm verification
Specify addresses to be verified
Exit Menu System
Resume Normal Operations
with
the
AutoSetup
August 2013