2-3.5 Step Five: Uploading The Application Program And Performing The Pre-Test; 2-3.6 Step Six: Performing Final System Test And Commissioning The System; 2-3.7 Step Seven: Installing The Actuation Devices And Extinguishing System; 2-3.8 Step Eight: Performing Final Installation Procedures - Kidde ARIES Installation, Operation And Maintenance Manual

Fire alarm/suppression
Table of Contents

Advertisement

these procedures and compare this list to the approved set of SLC devices. Correct
any inconsistencies and/or trouble messages.
2-3.5
Step Five: Uploading the Application Program and Performing the Pre-Test
Upload the site-specific application program, and pre-test the system in accordance with
the approved sequence of operation. Be sure that extinguishing-system actuation
devices are not connected to the extinguishing system during pre-testing.
2-3.6
Step Six: Performing Final System Test and Commissioning the System
Final test and commission the system in the presence of the owner and the authority
having jurisdiction. Be sure that extinguishing-system actuation devices are not
connected to the extinguishing system during final testing.
2-3.7
Step Seven: Installing the Actuation Devices and Extinguishing System
Connect the actuation devices to the extinguishing system per the procedures in the
applicable agent-storage-container installation manual.
2-3.8
Step Eight: Performing Final Installation Procedures
Install the front door when testing is completed, all appropriate occupancy certificates
have been secured, the end user has been thoroughly trained in the system operation,
and the system is armed and ready for service. Lock the front door and give the key to
the end user's designated personnel.