Level-3 And Lower-Level Event Display; What To Do When Level-3 And Lower-Level Messages Are Displayed - Kidde ARIES Installation, Operation And Maintenance Manual

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.8.7
Device Address 010
3-2.5.8.8
August 2013

Level-3 and Lower-Level Event Display

The upper line of the LCD display shows the activated device or circuit
address, the change of state, and the device or circuit type that reported
the event. The lower line indicates the numbers of concurrently-active
events for the following Level-3 through Level-5 event types:
Pre-Alarms
Alarm-Verification Countdowns
Supervisory Events
Troubles
Figure 3-32 shows the appearance of the display when more than one type
of Level-3 through Level-5 event is active.
010 VERIFY ON PHOTOELECTRIC (SCROLLTOVIEW)
PREALM 00
Figure 3-32. Typical Multiple Lower-Level Event Display
You may manually scroll the display among the active lower-level events,
according to the priority of events as described in Paragraph 3-2.5.8.7 by
using the <SCROLL> Key. Only Level-3 events will scroll if present. Level-
4 events scroll if there are no Level-3 events. Supervisory and trouble
events scroll if there are no active pre-alarms or alarm verifications.

What to Do When Level-3 and Lower-Level Messages are Displayed

Press the <SCROLL> Key to display the information for the highest-priority
and subsequent events. The display will show the 1st event when all of
current Level-3 and lower-level events have been manually displayed. The
upper line of the display will revert to showing the highest-priority event
approximately 5 seconds after the last press of the <SCROLL> Key. You
may then manually scroll the display among the active Level-3 through
Level-5 events.
The appearance of the display when manually scrolling through the
currently-active Level-3 and lower-level events is shown in Figure 3-33.
Device Address 062
062
FIRST FLOOR POWER ROOM
Device-Specific
Custom Message
Figure 3-33. Typical Level-3 and Lower-Level Events Display
Alarm Indication
Device Type Reporting Alarm
AVCNTDN 01
SPV 00
No. of Alarm-Verification Countdowns
No. of Pre-Alarms
Type of Fault
Device Type with Fault
OPEN ON
THERMAL
3-116
TBL 00
No. of Troubles
No. of Supervisory Events
P/N 06-236530-001