C-1
RELEASING CIRCUIT ELECTRICAL CHARACTERISTICS
The following electrical characteristics apply to the dedicated releasing circuits, Release 1 and
Release 2.
Characteristic
Maximum Devices.
Minimum Peak Firing Current
Maximum Steady Firing Current
Max. Open-Circuit Term. Voltage
Min. Open-Circuit Term. Voltage
Maximum Supervision Current
Dummy Load
C-2
COMBINATION CIRCUIT ELECTRICAL CHARACTERISTICS FOR RELEASING
The following electrical characteristics apply to the combination circuits, Combo 1 and Combo 2.
Characteristic
Maximum Devices
Minimum Peak Firing Current
Maximum Steady Firing Current
Max. Open-Circuit Term. Voltage
Min. Open-Circuit Term. Voltage
Maximum Supervision Current
Dummy Load
P/N 06-236530-001
APPENDIX C
Table C-1. Release 1 and 2 Circuit Electrical Characteristics
Table C-2. Combo 1 and 2 Circuit Electrical Characteristics
Listed and Approved Releasing Devices
Solenoids
2
2.8 A / 30 ms
2.4 A
28.0
20.0
5 ma
10 k Ohms
Solenoids
1
2.8 A / 30 ms
2.4 A
28.0
20.0
5 ma
10 k Ohms
C-1
Actuator
1
1.5 A / 10 ms
---
28.0
20.0
5 ma
---
Actuator
Do Not Use
---
---
---
---
---
---