Battery Calculations
Round up to next whole number (7 AH) using the largest-calculated battery capacity (6.86 AH)
for the required standby-battery size.
Use Table A-3 to determine the maximum standby currents that can be used as a function of
the required standby hours and the size of the battery used.
Table A-3. Maximum Standby Currents vs. Standby Duration and Battery Size
Standby Duration
(hrs.)
4
4
24
24
60
90
24
60
90
August 2013
Alarm Duration
Max. Standby
(min.)
5
5
5
5
5
10
5
5
10
Max. Alarm
Current (A)
Current (A)
1.4
2.5
0.4
1.2
0.5
0.3
2.6
1.0
0.6
A-4
Max. Battery (AH)
5.4
7
5.4
12
5.4
12
5.4
35
5.4
35
5.4
35
5.4
70
5.4
70
5.4
70