Kidde ARIES Installation, Operation And Maintenance Manual page 201

Fire alarm/suppression
Table of Contents

Advertisement

P/N 06-236530-001
3. Connect the standby batteries as shown in Figure 2-9. The display will
indicate the following messages:
DATE/TIME MUST BE SET TROUBLE ON
NORMAL OPERATION TEST
SLC NOT MONITORING ON
NORMAL OPERATION TEST
002 ACTIVE TROUBLES REMAIN
PRESS SCROLL TO VIEW
Figure 3-38. Boot-Up Message
Press the <ACKNOWLEDGE> Key to silence the buzzer and change the
Trouble LED from flashing to steady illumination.
These messages will scroll for several minutes.
Proceed to Step 4 after the "SLC Not Monitoring On" message disappears
and the number of active troubles changes from 002 to 001.
4. Set the time and date as follows:
a. Press the 0 Key. This display will show this message:
PLEASE ENTER PASSWORD
* * * * * *
Figure 3-39. Password Prompt
b. Press the default Level-1 Password (973480) keys and press the
<Enter> Key. The top-level menu will appear:
1: ISOLATE
2: LIST
3: SET
4: TEST
Figure 3-40. Top-Level Menu Selections
c. Press the 3 Key to select "SET"
1: TIME/DATE
3: SLC DEVICES
Figure 3-41. Set Menu
d. Press the 1 Key to select "TIME/DATE"
1: SET TIME
2: SET DATE
3: BATTERY
Figure 3-42. Time/Date Sub-Menu
e. Press the 1 Key again to select "SET TIME"
1: AM/PM
Figure 3-43. Sub-Menu for Time-Display Format
f.
Press the 1 Key again to select "AM/PM" format
2: PORT CONTROL
SCROLL FOR MORE
2: MILITARY
3-119
August 2013