Kidde ARIES Installation, Operation And Maintenance Manual page 153

Fire alarm/suppression
Table of Contents

Advertisement

3-2.5.2.4.51 How to Prevent the Outputs on a Networked Control Unit from Being
Step
1
Press 0 Key
2
Enter Password
3
Press 3 Key
4
Press "Scroll" Key
5
Press 6 Key
6
Press "Scroll" Key
7
Press 6 Key
8
Press 2 Key and then press "Enter" Key to confirm
selection.
9
Press "Backspace" Key (as required)
10
Wait until "Initializing Configuration" message
disappears from the display.
P/N 06-236530-001
Remotely Silenced by Another Control Unit
Purpose: To prevent the silenceable outputs on a networked control
unit from being silenced by other control units in the network. This
procedure restricts silencing of the outputs to the control unit itself.
Action
3-71
Result
Initiate menu access
Gain access to menus
Enter Set-Menu branch
Access additional options
Select "Network" option
Access additional options
Select "Silence"
Select "Disable"
Exit Menu System
Initialization complete
August 2013