Routings for Power-Limited and Non-Power-Limited Wiring
Use left-side gutter for non-
power-limited wiring.
Non-power-limited wiring
Non-power-limited
wiring
Note:
Route wiring as shown when combination power-limited and non-power-limited circuits are used.
Direct all non-power-limited wiring to the rear and then to the left-hand side of the enclosure. Tie wrap this wiring to the
back of the enclosure to maintain a minimum 1/4-inch separation from all power-limited wiring.
Direct all power-limited wiring outward and then to the right-hand side of the enclosure. Also tie wrap this wiring as
necessary to maintain a minimum 1/4-inch separation from all non-power-limited wiring.
August 2013
TB1
TB15
4 3 2 1
4 3 2 1
SLC
RS 485
USB B
RS-232 B
AC POWER
ALARM
PRE-ALARM
J10
TB3
+
+
Batt Out
240
Release 1
120
TB11
TB13
TB12
1 2 3 4
Maintain 1/4-in. separation as shown between power-
limited and non-power-limited wiring in this area.
Figure E-1. Power-Limited and Non-Power-Limited Wiring
J5
RS-232 A
J3
J8
SYSTEM
SYSTEM TROUBLE
SILENCE
ACKNOWLEDGE
SUPERVISORY
SYSTEM
SCROLL
SILENCE
RESET
1
2
3
4
5
6
7
8
9
0
TB14
TB5
1/4-in. (min.)
Release 2
Aux 24 VDC
Combo 1
Combo 2
TB2
TB7
TB6
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1/4-in. (min.)
A - A
A - A
E-2
Use right-side gutter for power-
limited wiring.
Power-limited wiring
Power-limited wiring
P/N 06-236530-001

Advertisement

Table of Contents
loading

Table of Contents