3-3.21.1.6
August 2013
Resynchronizing the Network
Some networked control units may occasionally retain alarm, supervisory
or trouble events from other control units in the network even if the events
have cleared from the other control units. This can be corrected by the
"Resynch Network" function that resynchronizes all messages across the
network.
Network events can be resynchronized by using a control unit configured
as Group 0, or by using
Another control unit in the same group as the control unit retaining
events
Any control unit in a network configured for global operation
The control unit itself
Use the following procedure to resynchronize the network:
1. Press the 0 Key on the keypad of the control unit being used to
resynchronize the network. This display will show this message:
PLEASE ENTER PASSWORD
* * * *
Figure 3-87. Password Prompt
2. Enter the Level-2 Password and then press the <Enter> Key. The
network-node prompt will appear as follows:
PRESS ENTER TO SELECT THE LOCAL NODE
OR ENTER NETWORK NODE NO. (1 - 32)*
Figure 3-88. Network Node Prompt
3. Select the local node by pressing the <Enter> Key, or enter a remote
node number then press the <Enter> Key. The top-level menu
selections will be displayed.
1: ISOLATE
3: SET
Figure 3-89. Top-Level Menu Selection
4. Press the 3 Key to select the Set sub-menu.
1: TIME/DATE
2: PRINTER CONTROL
3: SLC DEVICES
SCROLL FOR MORE
Figure 3-90. Set Sub Menu
5. Press the <SCROLL> Key, and then press the 4 Key to select
PROGRAMMING
4: PROGRAMMING
5: GLOBALS
6: NETWORK
SCROLL FOR MORE
Figure 3-91. Additional Set Menu Options