Initial Signaling-Line-Circuit Configuration - Kidde ARIES Installation, Operation And Maintenance Manual

Fire alarm/suppression
Table of Contents

Advertisement

3-2.6.3
August 2013
SET TIME (AM/PM)
ENTER THE TIME
Figure 3-44. Sub-Menu to Enter Current Time
g. Enter the time (HH = hours, 0-12; MM = minutes, 0-59) using the
digits keys. Press the <Enter> Key to finish your entry.
h. Press the 1 Key for AM or the 2 Key for PM as indicated below, and then
press the <Enter> Key to enter your selection:
SET TIME (AM/PM)
1: AM
Figure 3-45. Sub-Menu to Complete Current-Time Entry
The display will return to the sub-menu below when you press the
<BACKSPACE> Key:
1: SET TIME
3: BATTERY
Figure 3-46. Time/Date Sub-Menu
i.
Press the 2 Key to select "SET DATE"
SET DATE
ENTER THE DATE
Figure 3-47. Sub-Menu to Enter Current Date
j.
Enter the date (MM = month, 0-12; DD = day, 0-31, YY = year, 00-
99) using the digits keys.
k. Press the <ENTER> Key to finish your entry.
5. Press the <BACKSPACE> Key three times to exit from the menu operating
state. Confirm that no new trouble messages have appeared on the display.
6. Remove all power from the control unit by disconnecting the standby battery
first and then disconnecting the AC power in anticipation of initially
configuring the signaling line circuit.
Note: It will be necessary to enter the date and time each time that the ARIES
Control Unit is completely powered down.

INITIAL SIGNALING-LINE-CIRCUIT CONFIGURATION

Note: The following procedure assumes that all SmartOne devices have been
addressed with the Handheld Programmer or via the ARIES keypad. Refer
to Appendix D to address SmartOne devices through the Handheld
Programmer or to Paragraph 3-2.5.2.4.6 to address SmartOne devices via
the ARIES control unit's keypad.
Use this procedure to initially configure and check the number of SmartOne
devices connected to the SLC.
1. Connect the wiring for the SLC to Terminal Block TB1. Refer to Figure 1-3.
See also Figures 2-12, 2-15, and 2-16 for typical SLC wiring.
2. Power the control unit, and set the time and date, using the procedure
outlined in Paragraph 3-2.6.2.
3. All of the SmartOne devices connected to the SLC will report a not-registered
trouble message similar to the message shown in Figure 3-48:
*_:_ _ (HH:MM)
2: PM
*
2: SET DATE
*_-_ _-_ _ (MM-DD-YY)
3-120
P/N 06-236530-001