Free tec_ctrl 0 integral time / Ftec0 Tn

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the integral time (I component, integrating time constant) of the free technology controller 0.
Note
Value = 0: The integral time is disabled.
If the parameter is set to zero during operation, the I component retains its most recent value.
p11091

CO: Free tec_ctrl 0 limit maximum / Ftec0 lim max

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-200.00 [%]
Description:
Sets the maximum limit of the free technology controller 0.
Dependency:
See also: p11092
Note
The maximum limit must always be greater than the minimum limit (p11091 > p11092).
p11092

CO: Free tec_ctrl 0 limit minimum / Ftec0 lim min

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-200.00 [%]
Description:
Sets the minimum limit of the free technology controller 0.
Dependency:
See also: p11091
Note
The maximum limit must always be greater than the minimum limit (p11091 > p11092).
p11093

Free tec_ctrl 0 limit ramp-up/ramp-down time / Ftec0 lim r-u/r-dn

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00 [s]
Description:
Sets the ramp-up and ramp-down time for the maximum and minimum limit (p11091, p11092) of the free technology
controller 0.
Dependency:
See also: p11091, p11092
Note
The ramp-up/ramp-down times are referred to 100%.
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Calculated: -
Scaling: -
Unit selection: -
Max:
10000.000 [s]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
200.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
100.00 [s]
Parameters
7.2 Parameter list
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
30.000 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
100.00 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
0.00 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
1.00 [s]
899