Digi Connect IT 4 User Manual page 549

Hide thumbs Also See for Connect IT 4:
Table of Contents

Advertisement

Services
Digi Connect IT® 4 User Guide
ii. Set the port:
(config service modbus_gateway client test_modbus_client)>
socket port
(config service modbus_gateway client test_modbus_client)>
where port is an integer between 1 and 65535. The default is 502.
iii. Set the packet mode:
(config service modbus_gateway client test_modbus_client)>
socket packet_mode value
(config service modbus_gateway client test_modbus_client)>
where value is either rtu or ascii. The default is rtu.
iv. Set the maximum allowable time between bytes in a packet:
(config service modbus_gateway client test_modbus_client)>
socket idle_gap value
(config service modbus_gateway client test_modbus_client)>
where value is any number between 10 milliseconds and one second, and take
the format number{ms|s}.
For example, to set idle_gap to 20 milliseconds, enter 20ms.
v. Set the amount of time to wait before disconnecting the socket when it has
become inactive:
(config service modbus_gateway client test_modbus_client)>
inactivity_timeout value
(config service modbus_gateway client test_modbus_client)>
where value is any number of minutes or seconds up to a maximum of 15
minutes, and takes the format number{m|s}.
For example, to set inactivity_timeout to ten minutes, enter either 10m or
600s:
(config service modbus_gateway client test_modbus_client)>
inactivity_timeout 600s
(config service modbus_gateway client test_modbus_client)>
vi. Set the hostname or IP address of the remote host on which the Modbus
server is running:
(config service modbus_gateway client test_modbus_client)>
remote_host ip_address|hostname
(config service modbus_gateway client test_modbus_client)>
Modbus gateway