5.4.4 Output Signals (Control Panel: Menu M2 -> G2.3)
Table 28: Output Signals, G2.3
Index
Parameter
P2.3.1
(1)
Analog output 1 signal selec-
tion
P2.3.2
Analog output function
P2.3.3
Analog output filter time
P2.3.4
Analog output inversion
P2.3.5
Analog output minimum
P2.3.6
Analog output scale
P2.3.7
Digital output 1 function
P2.3.8
RO1 function
P2.3.9
RO2 function
52 | Danfoss A/S © 2023.02
Min
Max
Unit
Default
-
0.1
E.10
A.1
-
0
8
1
0.00
10.00
s
1.00
-
0
1
0
-
0
1
0
10
1000
%
100
-
0
22
1
-
0
22
2
-
0
22
3
Multi-step Speed Control
ID
Description
-
464
307
0 = Not used (20 mA/10 V)
1 = Output freq. (0–f
max
2 = Freq. reference (0–f
3 = Motor speed (0–Motor nominal speed)
4 = Motor current (0–I
nMotor
5 = Motor torque (0–T
6 = Motor power (0–P
nMotor
7 = Motor voltage (0–U
8 = DC-link volt (0–1000 V)
308
0 = No filtering
309
0 = Not inverted
1 = Inverted
310
0 = 0 mA (0 V)
1 = 4 mA (2 V)
-
311
312
0 = Not used
1 = Ready
313
2 = Run
3 = Fault
314
4 = Fault inverted
5 = AC drive overheat warning
6 = Ext. fault or warning
7 = Ref. fault or warning
8 = Warning
9 = Reversed
10 = Jogging speed selected
11 = At speed
12 = Mot. regulator active
13 = OP freq. limit superv. 1
14 = OP freq. limit superv.2
15 = Torque limit superv.
16 = Ref. limit superv.
17 = Ext. brake control
18 = Control place: I/O
19 = AC drive temp. limit superv.
20 = Unrequested rotation direction
21 = Ext. brake control inverted
22 = Thermistor fault/warn.
AB296635287482en-000301 / DPD00903
Application
)
)
max
)
)
nMotor
)
)
nMotor