VACON® NX All-in-One
Application Guide
3.4.5 Drive Control Parameters (Control Panel: Menu M2->G2.4)
Table 9: Drive Control Parameters, G2.4
Index
Parameter
P2.4.1
Ramp 1 shape
P2.4.2
Ramp 2 shape
P2.4.3
Acceleration time 2
P2.4.4
Deceleration time 2
P2.4.5
Brake chopper
P2.4.6
Start function
P2.4.7
Stop function
P2.4.8
DC braking current
P2.4.9
DC braking time at stop
P2.4.10
Frequency to start DC braking during
ramp stop
P2.4.11
DC braking time at start
P2.4.12
Flux brake
P2.4.13
Flux braking current
Danfoss A/S © 2023.02
Min
Max
Unit
Default
0.0
10.0
s
0.1
0.0
10.0
s
0.0
0.1
3000.0
s
1.0
0.1
3000.0
s
1.0
-
0
4
0
-
0
2
0
-
0
3
0
0.00
I
A
0.7 x I
L
0.00
600.00
s
0.00
0.10
10.00
Hz
1.50
0.00
600.00
s
0.00
-
0
1
0
0.00
I
A
I
L
H
Standard Application
ID
Description
500
0 = Linear
100 = full acc/dec inc/dec tmes
501
0 = Linear
100 = full acc/dec inc/dec tmes
-
502
-
503
504
0 = Disabled
1 = Used when running
2 = External brake chopper
3 = Used when stopped/running
4 = Used when running (no testing)
505
0 = Ramp
1 = Flying start
2 = Conditional flying start
506
0 = Coasting
1 = Ramp
2 = Ramp+Run enable coast
3 = Coast+Run enable ramp
-
507
H
508
0 = DC brake is off at stop
-
515
516
0 = DC brake is off at start
520
0 = Off
1 = On
-
519
AB296635287482en-000301 / DPD00903 | 23