Application Guide
A
B
ID716
E
F
Illustration 78: The Underload Time Counter Function
A
Underload time counter
B
Trip area
C
Trip/warning ID 713
10.349 (ID 717) Wait Time
Location in the menu: P2.8.1 (Standard Application, Local/Remote Control Application, Multi-step Speed Control Application, PID
Control Application, Multi-purpose Control Application, Pump and Fan Control Application
Use this parameter to set the wait time before the first reset is done.
10.350 (ID 718) Trial Time
Location in the menu: P2.8.2 (Standard Application, Local/Remote Control Application, Multi-step Speed Control Application, PID
Control Application, Multi-purpose Control Application, Pump and Fan Control Application
Use this parameter to set the trial time for the automatic reset function. During the trial time, the automatic reset function tries to
reset the faults that occur.
If the number of faults during the trial time exceed the value of the respective parameter set with ID 720 to ID 725, a permanent fault
is generated.
Danfoss A/S © 2023.02
C
D
D
Time
E
Underload
F
No underload
AB296635287482en-000301 / DPD00903 | 257