VACON® NX All-in-One
Application Guide
Troubleshooting
•
Reset unit.
•
Set the deceleration time longer.
•
Dimensioning of the brake chopper is not correct.
•
Use external brake resistor.
11.1.105 Fault 42 - Brake resistor overtemperature, Subcode S2 - Brake resistance too high (BCU)
Cause
Brake resistor overtemperature protection has detected too heavy braking.
Troubleshooting
•
Reset unit.
•
Set the deceleration time longer.
•
Dimensioning of the brake chopper is not correct.
•
Use external brake resistor.
11.1.106 Fault 42 - Brake resistor overtemperature, Subcode S3 - Brake resistance too low (BCU)
Cause
Brake resistor overtemperature protection has detected too heavy braking.
Troubleshooting
•
Reset unit.
•
Set the deceleration time longer.
•
Dimensioning of the brake chopper is not correct.
•
Use external brake resistor.
11.1.107 Fault 42 - Brake resistor overtemperature, Subcode S4 - Brake resistance not detected
(BCU)
Cause
Brake resistor overtemperature protection has detected too heavy braking.
Troubleshooting
•
Reset unit.
•
Set the deceleration time longer.
•
Dimensioning of the brake chopper is not correct.
•
Use external brake resistor.
11.1.108 Fault 42 - Brake resistor overtemperature, Subcode S5 - Brake resistance leakage (earth
fault) (BCU)
Cause
Brake resistor overtemperature protection has detected too heavy braking.
Troubleshooting
•
Reset unit.
•
Set the deceleration time longer.
•
Dimensioning of the brake chopper is not correct.
•
Use external brake resistor.
11.1.109 Fault 43 - Encoder fault, Subcode S1 - Encoder 1 channel A is missing
Cause
Problem detected in encoder signals.
Encoder channel A is missing.
344 | Danfoss A/S © 2023.02
Fault Tracing
AB296635287482en-000301 / DPD00903