Danfoss VACON NX All-in-One Application Manual page 272

Hide thumbs Also See for VACON NX All-in-One:
Table of Contents

Advertisement

VACON® NX All-in-One
Application Guide
Selec-
Function
tion
number
2
Wake up happens
when actual value
goes below the limit.
3
Wake up happens
when actual value
exceeds the limit.
10.424 (ID 1020) PID Controller Bypass
Location in the menu: P2.9.16 (Pump and Fan Control Application)
Use this parameter to select if the PID controller is bypassed.
Then the frequency of the controlled drive and the starting points of the auxiliary drives are defined according to the actual value
signal.
272 | Danfoss A/S © 2023.02
Limit
The limit defined with parameter ID
1018 is in percent of the current val-
ue of the reference signal.
The limit defined with parameter ID
1018 is in percent of the current val-
ue of the reference signal.
Parameter Descriptions
Description
Actual
value
signal
100%
reference=50%
Par. ID1018=60%
limit=60%*reference=30%
Start
Stop
Actual
value
signal
100%
Par. ID1018=140%
limit=140%*reference=70%
reference=50%
AB296635287482en-000301 / DPD00903
t
t
Start
Stop

Advertisement

Table of Contents
loading
Need help?

Need help?