VACON® NX All-in-One
Application Guide
Index
Parameter
P2.6.18.22
IW Offset
P2.6.18.23
Speed Step
P2.6.18.24
Torque Step
7.4.8 Motor Control Parameters, VACON® NXP (Control Panel: Menu M2 -> G2.6)
Table 75: Motor Control Parameters, G2.6
Index
Parameter
P2.6.1
Motor control mode
P2.6.2
Switching Frequency
P2.6.3
Overvoltage controller
P2.6.4
Undervoltage controller
P2.6.5
Motor control mode 2
P2.6.6
Load Drooping
P2.6.7
Identification
P2.6.8
Restart Delay
P2.6.9
Load Drooping Time
Negative Frequency Limit
P2.6.10
P2.6.11
Positive Frequency Limit
P2.6.12
Generator torque limit
P2.6.13
Motoring torque limit
108 | Danfoss A/S © 2023.02
Min
Max
-32000
32000
-50.0
50.0
-300.0
300.0
Min
Max
Unit
-
0
4
10
Varies
kHz
-
0
2
-
0
2
-
0
4
0.00
100.00
%
-
0
6
100
60000
s
0
32000
ms
-
-327.67
P2.6.11
-
P2.6.10
327.67
0.0
300.0
%
0.0
300.0
%
Multi-purpose Control Application
Unit
Default
ID
-
0
670
-
0.0
1252
-
0.0
1253
Default
ID
Description
0
600
0 = Frequency control
1 = Speed control
2 = Open loop torque control
3 = Closed loop speed ctrl
4 = Closed loop torque control
-
Varies
601
1
607
0 = Not used
1 = Used (no ramping)
1
608
2 = Used (ramping)
2
521
See P2.6.1
-
0.00
620
0
631
0 = No action
1 = Identification w/o run
2 = Identification with run
3 = Encoder ID Run (PMSM)
4 = Ident All
5 = DTC Ident
6 = ID Run Failed
-
Varies
1424
-
0
656
-327.67
1286
0 = Disabled
1 = Enabled
-
327.67
1285
-
300.0
1288
-
300.0
1287
AB296635287482en-000301 / DPD00903