Site Requirements (New Main Way) - Huawei FusionModule5000 Series Installation Manual

Smart modular data center single-row aisle containment with 2000 mm high cabinets, ecc800
Hide thumbs Also See for FusionModule5000 Series:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
Smart module layout requirement
Figure 1-4
Figure 1-4 Smart module layout requirement

1.5 Site Requirements (New Main Way)

Equipment Room Height Requirement
Figure 1-5
high cabinets and the new main way are used.
The clearance for fire extinguishing nozzles is subject to specific fire extinguishing
requirements and is not considered in this section.
Table 1-2 Equipment Room Net Height Requirement (Without Base)
Scenario
2000 mm high cabinets and the new main
way
Issue 01 (2019-03-05)
shows the layout requirement for the smart module.
shows the height of each component in single-row aisle containment if 2000 mm
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1 Installation Preparations
Equipment room net height
> 2800 mm
6