Huawei FusionModule5000 Series Installation Manual page 142

Smart modular data center single-row aisle containment with 2000 mm high cabinets, ecc800
Hide thumbs Also See for FusionModule5000 Series:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
After a magnetic lock is installed, the cover can be discarded.
1.
Remove the cover at the rear of the mounting kit above the door, remove the four screws
at the bottom of the mounting kit, and keep the screws aside, as shown by (1) in
9-33.
2.
Remove the mounting plate of the magnetic lock cover, as shown by (2) in
3.
Remove the four screws on the mounting plate of the magnetic lock cover, and remove
the cover of the magnetic lock, as shown by (3) in
Figure 9-33 Removing the cover of the magnetic lock
Step 2 Remove the magnetic lock fixing plate. Remove the fixing plate from the revolving door
magnetic lock using the hex key delivered with the magnetic lock.
Four hex socket screws need to be removed in this step.
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 Installing Monitoring Devices
Figure
9-33.
Figure
Figure
9-33.
133