FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
Figure 8-8 Installing an interconnecting wrench
(1) Interconnecting wrench
Step 8 Install the cable trough above the rear door in a similar way.
----End
8.2 Installing a 300 mm Wide Cable Trough
Context
A 300 mm wide cable trough is installed on the top of a 300 mm wide cabinet after a 600 mm
wide cable trough is installed.
Figure 8-9
Issue 01 (2019-03-05)
shows a 300 mm wide cable trough. Its BOM number is 21501141.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 (Optional) Installing Cable Troughs
109