Huawei FusionModule5000 Series Installation Manual page 111

Smart modular data center single-row aisle containment with 2000 mm high cabinets, ecc800
Hide thumbs Also See for FusionModule5000 Series:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
Figure 6-32 Interconnecting light tubes
Procedure
Step 1 Secure light holders to the skylight plate using M3 screws, as shown by (1) in
Figure 6-33 Installing a light tube
Step 2 Install a light tube onto the holders, as shown by (2) in
Issue 01 (2019-03-05)
Ensure that each light tube is secured by three holders.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Installing the Contained Aisles
Figure
Figure
6-33.
6-33.
102