4.2.2 Checking the Air Pressure

Context
The device has been injected with 0.3–0.5 MPa nitrogen before delivery. Check the air
pressure for Nitrogen leakage.
Procedure
Step 1 Open the rear door.
Step 2 Remove the air filters.
1.
Issue 01 (2019-03-05)
NetCol
5000-
C030H
6
NetCol
5000-
C030H
7
without
heating
and
humidif
ication
NetCol500
0-C030H7
with
heating
and
humidificat
ion
Unfasten the eight rotating check plates in the upper and lower positions of the air filters,
as shown in
Figure
4-27.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Specifications
Minimum specifications for the
active and standby routes: AC
circuit breaker, 230/400 V, 10 A,
2P, C feature
Minimum specifications for the
common power cable: AC circuit
breaker, 230/400 V, 40 A, 2P, C
feature
Minimum specifications for the
backup power cable: AC circuit
breaker, 230/400 V, 10 A, 2P, C
feature
10 m
≥ 6 mm
2
4 Hardware Installation Preparations
Quantit
Remarks
y
1 PCS
Engineering
purchasing
1 PCS
Engineering
purchasing
1 PCS
Engineering
purchasing
1 PCS
Standard
configuratio
n; delivered
with the
product
1 PCS
Engineering
purchasing
43