Figure 4-24 Pipe support (unit: mm)
The water inlet pipe can be connected for a humidifier in two ways, as shown in
Issue 01 (2019-03-05)
Name
gauge bend
Water
pressure
gauge and
thermometer
Height of the U-shaped clamp (H) = Pipe diameter (with thermal insulation foam) – 5 mm.
When the pipe is straight, add a support every 2500 mm. When the direction of the pipe is changed,
add a support at the position that is 1000 mm away from the changing point.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Specifications
Precision level: 2.5
Operating environment: –40° C
to +70° C
Temperature influence: ≤
0.4%/10° C (operating
temperature: 20° C± 5° C)
Test pressure range: 1.2–2.5
MPa
4 Hardware Installation Preparations
Remarks
the system solution
Engineering
purchasing, based on
the system solution
Figure
4-25.
39