Figure A-8 Column occupying part of a cabinet place (A < 800 mm and B ≥ 400 mm)
Issue 01 (2019-03-05)
Cabinet places on the column side are left blank and sealed by sealing plates. Directions of the
concave sides of the sealing plates are shown in
Install cable trays over the cabinets on both sides of the blank cabinet place for routing strong-
current and weak-current cables.
Install an adjustable skylight over the aisle containment. The area to be covered by the adjustable
skylight is shown in