Procedure
Step 1 Move away the base and install expansion bolts, as shown in
Figure 4-9 Installing an expansion bolt (unit: mm)
Step 2 Measure the hole depths and distances. If any deviation is found, mark the positions again and
drill new holes.
Step 3 Deploy the base again, adjust the base position, and partially tighten the expansion bolts.
Step 4 Measure the levelness of the base using a level, as shown by (1) in
Step 5 If the base is not level, put spacers under it, as shown by (2) in
Step 6 Tighten the four expansion bolts using a torque wrench, as shown by (3) in
Figure 4-10 Leveling the fixed base
Step 7 Secure other bases in the same way.
Step 8 After securing bases, connect bases using connecting plates, as shown by (1) in
and secure the screws to the floor holders on the bases, as shown by (2) in