Huawei FusionModule5000 Series Installation Manual page 102

Smart modular data center single-row aisle containment with 2000 mm high cabinets, ecc800
Hide thumbs Also See for FusionModule5000 Series:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
Step 4 Adjust the gap between door panels.
After the door panels are installed and closed, the gap between panels may be uneven and
look ungraceful, as described in
Table 6-2 Door gap faults
Fault Type
Tilted door panel
Varying gap between door
panel and door header
Door mismatch
1.
Figure 6-20
Both methods must ensure that there is no gap between the post bottom and the floor.
Issue 01 (2019-03-05)
Table
shows a tilted door. You can solve the problem in the following ways:
If the door tilts by a large degree, adjust the anchor bolts of the cabinet. If a post is
lifted off the floor due to the adjustment, add a spacer under the post.
If the door slightly tilts, add a pad under the corresponding post to correct the tilt.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6-2. If the gaps are even, skip this procedure.
Root Cause
The left and right cabinets
onto which the upper frame
mounting kit is hung are not
on the same level, or the
upper frame mounting kit
and posts are tilted because
the floor is uneven.
One post has tilted, or the
door does not match with
the upper frame mounting
kit due to a manufacturing
error.
The left and right cabinets
onto which the upper frame
is hung are not on the same
level.
6 Installing the Contained Aisles
Solution
For details about the
adjusting method, see
4.1.
For details about the
adjusting method, see
4.2.
For details about the
adjusting method, see
4.3.