Huawei FusionModule5000 Series Installation Manual page 161

Smart modular data center single-row aisle containment with 2000 mm high cabinets, ecc800
Hide thumbs Also See for FusionModule5000 Series:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
Figure 9-57 Layout of smart ETH gateways in scenario 1
Table 9-5 Scenario 2
Scenario
Figure 9-58 Layout of smart ETH gateways in scenario 2
Table 9-6 Scenario 3
Scenario
Rack environment unit deployed
Issue 01 (2019-03-05)
No rack environment unit deployed
Module length > 7 m; number of air
conditioners > 4
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 Installing Monitoring Devices
Rules for Deploying Smart ETH
Gateways
Deploy 2 PCS for each end cabinet and IT
cabinet in the middle in the smart module,
not for other cabinets. A total of 6 PCS
should be deployed, as shown in
58.
Rules for Deploying Smart ETH
Gateways
Deploy 2 PCS for each end cabinet and 1
PCS for every three cabinets among other
cabinets in the smart module, as shown in
Figure
9-59.