FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
Figure A-23 Securing an adjustable skylight side sealing plate
----End
A.5.5.4 Installing the PC Plate Support and PC Plate
Procedure
Step 1 Select positions for installing PC plate supports. As shown in
should be installed closely to the column, and PC plate support 2 should be installed in the
middle between PC plate support 1 and the edge of the adjustable skylight.
Issue 01 (2019-03-05)
If the space between the right side of the column and the right side of the adjustable skylight is less than
600 mm, PC plate support 2 does not need to be installed.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
A Appendix
Figure
A-24, PC plate support 1
218