Name
Specifications
The thickness of thermal
insulation foam wrapping main
chilled water supply and return
pipes (DN80): ≥ 40 mm.
Glue for
Armaflex 820
wrapping
pipes with
thermal
insulation
foam
Black rubber
Recommended thickness > 3 mm
adhesive with
thermal
insulation
foam
Joint sealant
The specifications of the sealant or
seal tape for screw threads are as
follows:
Applicable to all pipe materials
Anaerobic metal pipe thread
sealant with PTEF as the
padding
Glycol solution resistant, fit for
threads and pipes
Maximum gap: 0.5 mm
Pressure resistance: above 3
MPa
Compliant with the industry
standard JB/T7311-2008
Technical Specification for the
Application of Anaerobic Glue in
Engineering Machinery
Flange and
DN80
sealing gasket
Butterfly
DN80, pressure resistance: 2.0 MPa
valve
or more
Copper gate
DN25, each for main chilled water
valve
supply and return pipes, pressure
resistance: 2.0 MPa or more
Y-shaped
Recommended: pressure resistance
strainer
of 2.0 MPa or more, 20 filtration
pores, installed on the main chilled
water supply pipe
Water
N/A
pressure
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Hardware Installation Preparations
Remarks
Engineering
purchasing
Engineering
purchasing
Engineering
purchasing
Engineering
purchasing
Engineering
purchasing
Engineering
purchasing
Engineering
purchasing, based on
pipes reserved onsite
Engineering
purchasing, based on