Optional) Installing Aisle Lights - Huawei FusionModule5000 Series Installation Manual

Smart modular data center single-row aisle containment with 2000 mm high cabinets, ecc800
Hide thumbs Also See for FusionModule5000 Series:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)

6.5 (Optional) Installing Aisle Lights

Context
Install aisle lights in parallel. Connect the first and last light tubes on aisle sides in series.
Install the light tubes on the skylight plates.
The BOM number for an aisle light tube is 52220134.
Figure 6-31 Layout of aisle lights
(1) Light tube
A light tube has male and female connectors at both ends for interconnection, as shown in
Figure
direction (also the female connectors) for serial connection of light tubes.
Issue 01 (2019-03-05)
A light tube is 872 mm long. Determine the distance (W) between a light tube and a side of the aisle
based on the actual length of the contained aisle in the module: W = (L – 872 x N)/2. L is the actual
length of the contained aisle. N is the number (round down the value of L/872) of light tubes installed in
a single row. Round down the value of W.
A maximum of 12 aisle lights can be connected in series. If the number exceeds 12, they should be
installed in different groups.
Redundant LED indicators are delivered.
Grouping rule: Divide into equal groups if possible and ensure that the light cables are routed out of
the nearby cable holes in skylight plates.
6-32. When installing lights, ensure that all the male connectors face the same
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Installing the Contained Aisles
Figure 6-31
shows the layout of the aisle lights.
101