FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
Context
Procedure
Step 1 Use two M5x10 tapping screws to secure the T/H sensor base to the IT cabinet door frame 1.8
m above the ground.
Step 2 Mount the T/H sensor onto the base.
Figure 9-66 Installing a T/H sensor
----End
Issue 01 (2019-03-05)
A T/H sensor is installed on the cabinet door frame post 1.8 m above the ground, as
shown in
Figure
9-66.
If the air conditioner implements cold-aisle control, install the temperature and humidity
sensor on the door frame of the IT cabinet front door. If the air conditioner implements
hot-aisle control, install the temperature and humidity sensor on the door frame of the IT
cabinet rear door.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 Installing Monitoring Devices
158