Figure 9-61 Installing temperature sensors
(A) Rack environment unit
----End

9.11 Rules for Deploying T/H Sensors

Context
Issue 01 (2019-03-05)
When installing temperature sensors on the front door, route the sensors through the
sponge strips between the rack rail and side plate, and then secure the sensors.
When installing temperature sensors, bind the cables behind the sensors to the cabinet,
keeping them 20 mm away from the sensor probes.
The temperature sensor must not be in touch with metal parts or cabinets.
Ensure that the temperature sensors are installed on the side without a PDU2000 on the
cabinet rear.
Keep the temperature sensors facing the inside of the cabinets to ensure accurate
measurement of cabinet interior temperatures.
Determine the number of T/H sensors to be deployed based on the number of air
conditioners.
Each air conditioner can be configured with three more external T/H sensors.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.