FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)

6.1 Installing Sealing Plates

Context
Sealing plates are used to seal the aisle. Different types of sealing plates are used for cabinets
with different sizes.
If sealing plates should be less than 300 mm away from a wall, adjust the installation
sequence of the aisle containment.
1. Secure the sealing plates and skylight connective plates for the end cabinets.
2. Secure the sealing plates to the floor.
3. Install the skylights.
4. Install other sealing plates and skylights in the same way.
Procedure
Step 1 Determine the position for installing sealing plates using a measuring tape and marker based
on the engineering layout diagram, as shown in
Issue 01 (2019-03-05)
6

Installing the Contained Aisles

Sealing plates 21500707 apply to cabinets that are 300 mm wide and 2000 mm high.
Sealing plates 21500718 apply to cabinets that are 600 mm wide and 2000 mm high.
Sealing plates 21500720 apply to cabinets that are 800 mm wide and 2000 mm high.
When determining the position, verify that adjacent sealing plates will be in close contact with each
other.
The distance between the cabinet front frame and the outer sealing plate is 1290 mm.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Installing the Contained Aisles
Figure
6-1.
77