FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
(7) Telescopic edges
A.5.5.1 Installing the Skylight Connective Plate
Prerequisites
The sealing plates near the aisle have been installed and secured.
Procedure
Step 1 Secure skylight connective plates to sealing plates or cabinets using eight M8 bolts.
Figure A-16 Installing a skylight connective plate
(1) Column
----End
A.5.5.2 Installing the Telescopic Edges
Procedure
Step 1 Extend the two telescopic edges to an appropriate length and secure them using two M6
screws.