FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
Figure 9-34 Removing the fixing plate of a magnetic lock
Step 3 Install the magnetic lock fixing plate. Secure the magnetic lock fixing plate to the upper frame
mounting kit using eight M4 countersunk screws, as shown by (1) in
Pay attention to the orientation of the magnetic lock fixing plate, and ensure that the protruded
surface of the magnetic lock faces the magnet.
Step 4 Install the magnetic lock. Route cables of the magnetic lock into the upper frame mounting
kit, and secure the magnetic lock to the fixing plate using the hex key delivered with the
magnetic lock, as shown by (2) in
Figure 9-35 Installing a magnetic lock
Step 5 Install the mounting plate of the magnetic lock cover, as shown in
Issue 01 (2019-03-05)
Figure
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 Installing Monitoring Devices
9-35.
Figure
9-35.
Figure
9-36.
134