Correct Method for Connecting Battery Cables
Issue 01 (2019-03-05)
Figure 12-25 Attaching the battery label
Route and secure cables between layers along the rack rail in the vertical direction, as
shown by (1) in
Figure
12-26.
Route and secure cables between layers along the tray supporting beam in the horizontal
direction, as shown by (2) in
Figure 12-26 Cable routes
(Optional) When battery cabinets are installed adjacent to each other, remove the upper
side plates from the battery cabinets for routing cables to the corresponding ports.
When the length of a battery cable equals the distance between two battery terminals,
connect the cable straight through, as shown in
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
12-26.
Figure
12 Cable Routing
12-27.