FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
12.2 Cable Routes for the Single-Row Aisle Containment
Scenario (Power Supply and Distribution Cabinet)
Figure 12-9
containment.
Ensure that strong-current cables and weak-current cables are at least 100 mm away from
each other.
Issue 01 (2019-03-05)
Figure 12-8 Direction for securing cable ties
shows how power cables and signal cables are routed in the single-row aisle
Huawei Proprietary and Confidential