FusionModule2000 Smart Modular Data Center
Installation Guide (2000 mm High Cabinets, Single-Row
Aisle Containment, 380 V)
1.4 Site Requirements
Equipment Room Height Requirement
The net height of an equipment room must not be lower than 2600 mm in the case of a
single-row aisle containment. The maximum module height includes the size of open
skylights and does not vary depending on the camera support and fire extinguisher support, as
shown in Figure 1-3.
The clearance for fire extinguishing nozzles is subject to specific fire extinguishing
requirements and is not considered in this section.
Table 1-2 Equipment room net height requirement (without bases)
Scenario
2000 mm high cabinet
When the bases are configured, the equipment room net height equals the equipment room net
height (without bases) plus the base height.
Issue 04 (2017-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1 Installation Preparations
Equipment Room Net Height
> 2600 mm