FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
Step 5 Place adjacent sealing plates in the same way.
Step 6 Interconnect adjacent sealing plates using three M6x16 screws with flat washers and nuts, as
shown by (3) in
Step 7 Install other sealing plates in the same way.
----End
6.2 Installing Skylights
6.2.1 Skylight Overview
6.2.1.1 600 mm Wide Control Skylight
Figure 6-2
Figure 6-2 600 mm wide control skylight
(1) Skylight connective plate
Issue 01 (2019-03-05)
If the floor is concrete, secure the 600 mm and 800 mm wide sealing plates to the floor
using M12x60 expansion bolts.
The number of screws for securing sealing plates must be same as the number of
corresponding holes in the lower end of the plates.
Figure
6-1.
shows a 600 mm wide control skylight. Its BOM number is 21242009.
The 600 mm wide control skylight is used to install monitoring components such as the camera,
multi-functional sensor, or smoke detector. It is used with 600 mm wide cabinets at the end of the
smart module.