Huawei FusionModule5000 Series Installation Manual page 68

Smart modular data center single-row aisle containment with 2000 mm high cabinets, ecc800
Hide thumbs Also See for FusionModule5000 Series:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
Step 4 Remove the hinges and connecting plates from the PDC rear door, as shown in
Put aside the hinges and connecting plates as they are needed in follow-up installation
processes.
Figure 4-44 Removing the PDC rear door mounting kit
Step 5 Move the tail frame installed with accessories and upper sealing plates to the cabinet rear
door, and adjust the anchor bolts of the tail frame so that the fail frame top is flush with the
cabinet top.
Step 6 Secure the tail frame to the PDC using eight M5 tapping screws, as shown in