INVT Goodrive35 Series Operation Manual page 85

Closed-loop vector control vfd
Table of Contents

Advertisement

Goodrive35 Series Closed-loop Vector Control VFD
Functio
Name
n code
P05.30
HDI switch-on delay
P05.31
HDI switch-off delay
P05.32
Lower limit of AI1 The function code defines the relationship between
Corresponding
P05.33
setting of the lower
limit of AI1
P05.34
Upper limit of AI1
Corresponding
P05.35
setting of
the upper limit of AI1
P05.36 AI1 input filter time
P05.37
Lower limit of AI2
Corresponding
P05.38
setting of lower limit
of AI2
P05.39
Upper limit of AI2
Corresponding
P05.40
setting of
upper limit of AI2
P05.41 AI2 input filter time
P05.42
Lower limit of AI3
Corresponding
P05.43
setting of lower limit
of AI3
Zero-drift value of
P05.44
AI3
Zero-point deadzone
P05.45
voltage of AI3
P05.46
Upper limit of AI3
Corresponding
P05.47
setting of upper limit
of AI3
P05.48 AI3 input filter time
Detailed instruction of parameters
the analog input voltage and its corresponding set
value. If the analog input voltage beyond the set
minimum or maximum input value, the VFD will
count at the minimum or maximum one.
When the analog input is the current input, the
corresponding voltage of 0–20mA is 0–10 V.
In different cases, the corresponding rated value of
100.0% is different. See the application for detailed
information.
The figure below illustrates different applications:
100%
-10V
AI3
Input filter time: this parameter is used to adjust the
sensitivity of the analog input. Increasing the value
properly can enhance the anti-interference of the
analog, but weaken the sensitivity of the analog
input.
Note: Analog AI1 and AI2 can support 0–10 V or
0–20mA input, when AI1 and AI2 selects 0–20mA
input, the corresponding voltage of 20mA is 5 V. AI3
can support the output of -10 V–+10 V.
The setting range of P05.32: 0.00 V–P05.34
The setting range of P05.33: -300.0%–300.0%
The setting range of P05.34: P05.32–10.00 V
The setting range of P05.35: -300.0%–300.0%
The setting range of P05.36: 0.000s–10.000s
78
Corresponding setting
AI
0
10V
20mA
AI1/AI2
-100%
Function parameters
Default
Modif
value
y
0.000 s
0.000 s
0.00 V
0.0%
10.00 V
100.0%
0.030s
0.00 V
0.0%
10.00 V
100.0%
0.100s
-10.00
V
-100.0
%
0.00 V
0.04 V
10.00 V
100.0%
0.030 s

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive35 Series and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Goodrive gd35-1r5g-4-c1Goodrive gd35-2r2g-4-c1 gd35-2r2g-4-d1Goodrive gd35-1r5g-4-d1Goodrive gd35-2r2g-4-h1Goodrive gd35-004g-4-c1Goodrive gd35-1r5g-4-h1 ... Show all

Table of Contents

Save PDF