8.1 What this chapter contains
This chapter tells how to reset faults and view fault history. It also lists all alarm and fault messages
including the possible cause and corrective actions.
 Only qualified electricians are allowed to maintain the VFD. Read the safety
instructions in chapter Safety precautions before working on the VFD.
8.2 Alarm and fault indications
Fault is indicated by LEDs. See Chapter 5 "Keypad operation procedures". When TRIP light is on, an
alarm or fault message on the panel display indicates abnormal VFD state. Using the information
given in this chapter, most alarm and fault cause can be identified and corrected. If not, contact the
INVT office.
8.3 How to reset
The VFD can be reset by pressing the keypad key STOP/RST, through digital input, or by switching
the power light. When the fault has been removed, the motor can be restarted.
8.4 Fault history
Function codes P07.27–P07.32 store 6 recent faults. Function codes P07.33–P07.40, P07.41–P7.48,
P07.49–P07.56 show drive operation data at the time the latest 3 faults occurred.
8.5 Fault instruction and solution
Do as the following after the VFD fault:
1. Check to ensure there is nothing wrong with the keypad. If not, contact the local INVT office.
2. If there is nothing wrong, please check P07 and ensure the corresponding recorded fault
parameters to confirm the real state when the current fault occurs by all parameters.
3. See the following table for detailed solution and check the corresponding abnormal state.
4. Eliminate the fault and ask for relative help.
5. Check to eliminate the fault and carry out fault reset to run the VFD.
8.5.1 VFD faults and solutions
Code
Fault
Inverter unit U
OUt1
phase protection
Inverter unit V
OUt2
phase protection
Inverter unit W
OUt3
phase protection

Chapter 8 Fault tracking

Cause
The acceleration is too fast
There is damage to the internal
to IGBT of the phase
Misoperation
is
interference.
The connection of the driving
wires is not good
Short-to-ground occurs.
 Increase acceleration time
 Change the power unit
caused
by
 Check the driving wires
 Check if there is strong interference
to the external equipment
200
Fault tracking
Solution

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive35 Series and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Goodrive gd35-1r5g-4-c1Goodrive gd35-2r2g-4-c1 gd35-2r2g-4-d1Goodrive gd35-1r5g-4-d1Goodrive gd35-2r2g-4-h1Goodrive gd35-004g-4-c1Goodrive gd35-1r5g-4-h1 ... Show all

Table of Contents

Save PDF