Goodrive35 Series Closed-loop Vector Control VFD
Model
GD35-280G-6-C1/D1/H1
GD35-315G-6-C1/D1/H1 95*2P
GD35-350G-6-C1/D1/H1 95*2P
GD35-400G-6-C1/D1/H1 150*2P
GD35-500G-6-C1/D1/H1 95*4P 95*2P
GD35-560G-6-C1/D1/H1 95*4P 95*4P
GD35-630G-6-C1/D1/H1 150*4P 150*2P
Note:
1. Cables of the sizes recommended for the main circuit can be used in scenarios where the ambient
temperature is lower than 40° C, the wiring distance is shorter than 100 m, and the current is the rated
current.
2. The terminals P1, (+), and (-) are used to connect to DC reactors and brake accessories.
D.4.3 Routing the cables
Motor cables must be arranged away from other cables. The motor cables of several VFDs can be
arranged in parallel. It is recommended that you arrange the motor cables, input power cables, and
control cables separately in different trays. The output dU/dt of the VFDs may increase
electromagnetic interference on other cables. Do not arrange other cables and the motor cables in
parallel.
If a control cable and power cable must cross each other, ensure that the angle between them is 90
degrees.
The cable trays must be connected properly and well grounded. Aluminum trays can implement local
equipotential.
The following figure shows the cable arrangement distance requirements.
Recommended
2
cable size (mm
)
RST
RST
PE
UVW
UVW
240
120
240–300 240–300 70–300 120–240
95*2P
120
–150*2P
95*2P
150
–150*2P
150*2P
150
–300*2P
95*4P
–150*4P
95*4P
–150*4P
150*4P
–300*4P
Connecting cable size (mm
PB (+),
P1, (+)
(-)
95*2P
95*2P
–150*2P
–150*2P
95*2P
95*2P
–150*2P
–150*2P
95*2P
95*2P
–150*2P
–150*2P
95*4P
95*4P
–150*4P
–150*4P
95*4P
95*4P
–150*4P
–150*4P
150*4P
150*4P
–300*4P
–300*4P
276
Optional peripheral accessories
2
)
Tightening
Terminal
screw
PE
120–300
150–300
150–300
95*2P
–150*2P
95*4P
–150*4P
150*4P
–240*4P
torque
(Nm)