Goodrive35 Series Closed-loop Vector Control VFD
Terminalname
Terminalname
Terminalname
Terminalname
current output is depended on the jumper. AO1 is switched by J1
and AO2 is switched by J2
AO2
2. Deviation±1%, 25° C
RO1A
RO1 relay output; RO1A is NO, RO1B is NC, RO1C is common
RO1B
port
Contact capacity: 3A/AC250V, 1A/DC30V
RO1C
RO2A
RO2 relay output; RO2A is NO, RO2B is NC, RO2C is common
RO2B
port
Contact capacity: 3A/AC250V, 1A/DC30V
RO2C
1. Switch capacity: 200mA/30V;
HDO
2. Range of output frequency: 0–50kHz
COM
Common port of +24V
CME
Common port of open collector output
1. Switch capacity: 200mA/30V;
Y
2. Range of output frequency: 0–1kHz
485+
For 485 communication port, 485 differential signal port and
standard 485 communication interfaces, use twisted pairs or
shielded cables.
485-
PE
Grounding terminal
PW
Provide input digital working power from external to internal;
Description