Goodrive35 Series Closed-loop Vector Control VFD
Functio
Name
n code
Overvoltage stall
P11.03
protection
Voltage protection of
P11.04
overvoltage stall
Current limit action
P11.05
selection
Automatic current
P11.06
limit
Frequency-decreasi
P11.07
ng ratio during
current limit
Detailed instruction of parameters
switching of the grid.
2. Prohibition of input phase loss protection can
enable this function.
0: Disable
1: Enable
DC bus voltage V
Overvoltage stall
threshold
Output
frequency
120–150% (standard bus voltage) (380 V)
120–150% (standard bus voltage) ( 660 V)
The actual increasing ratio of motor speed is lower
than the ratio of output frequency because of the big
load during ACC running. It is necessary to take
measures to avoid overcurrent fault and the VFD
trips.
Ones: current limit setting
0: Invalid
1: Valid
During the running of the VFD, it will detect the
output current and compare it with the limit level
defined in P11.06. If it exceeds the level, the VFD
will run at stable frequency in ACC running, or the
VFD will derate to run during the constant running. If
it exceeds the level continuously, the output
frequency will keep on decreasing to the lower limit.
If the output current is detected to be lower than the
limit level, the VFD will accelerate to run.
104
Function parameters
Default
Modif
value
0
Time t
Time t
136%
120%
1
160.0%
10.00
Hz/s
y

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive35 Series and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Goodrive gd35-1r5g-4-c1Goodrive gd35-2r2g-4-c1 gd35-2r2g-4-d1Goodrive gd35-1r5g-4-d1Goodrive gd35-2r2g-4-h1Goodrive gd35-004g-4-c1Goodrive gd35-1r5g-4-h1 ... Show all

Table of Contents

Save PDF