Goodrive35 Series Closed-loop Vector Control VFD
Functio
Name
n code
P01.08
Stop mode
Starting frequency of
P01.09
DC brake
P01.10 Demagnetizing time
P01.11
DC brake current
P01.12
DC brake time
Dead time of
P01.13
FWD/REV rotation
Detailed instruction of parameters
0: Decelerate to stop: after the stop command
becomes valid, the VFD decelerates to decrease the
output frequency during the set time. When the
frequency decreases to P01.15, the VFD stops.
1: Coast to stop: after the stop command becomes
valid, the VFD ceases the output immediately. And
the load coasts to stop at the mechanical inertia.
The starting frequency of stop brake: The VFD will
carry on stop DC brake when the frequency is
arrived during the procedure of decelerating to stop.
Demagnetizing time: Before the stop DC brake, the
VFD will close output and begin to carry on the DC
brake after the waiting time. This function is used to
avoid the overcurrent fault caused by DC brake
when the speed is too high.
Stop DC brake current: the DC brake added. The
stronger the current, the bigger the DC brake effect.
The brake time of stop brake: the retention time of
DC brake. If the time is 0, the DC brake is invalid.
The VFD will stop at the set deceleration time.
Acceleration
P01.04
P13.14
P01.23
Setting range of P01.09: 0.00 Hz–P00.03 (max.
output frequency)
Setting range of P01.10: 0.00–30.00s
Setting range of P01.11: 0.0–100.0%
Setting range of P01.12: 0.0–50.0s
During the procedure of switching for/rev rotation,
set the threshold by P01.14, which is as the table
below:
55
P01.09
P13.15
Constant speed
Deceleration
P01.12
P01.10
In running
Function parameters
Default
Modif
value
○
0
○
0.00 Hz
○
0.00 s
○
0.0%
○
0.0 s
Time t
0.0 s
○
y