Parameters - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Functions, monitoring, and protective functions
9.2 Drive functions
9.2.6.3

Parameters

• p0352
• p1200
• p1202
• p1203
• r1204
• r1205
Note
Set search direction for the flying restart
For p1200 = 1, 2, 3, the following applies: Search in both directions, start only in the setpoint
direction.
For p1200 = 4, 5, 6, the following applies: Search only in the setpoint direction.
500
WARNING
Danger to life as a result of unexpected motor movement when activating flying restart
When the flying restart (p1200) function is active, the drive may still be accelerated by
the search current despite the fact that it is at standstill and the setpoint is 0!
For this reason, death, serious injury, or considerable material damage can occur if
personnel enter the working area of a motor in this state.
• Observe the general safety instructions.
• Ensure that the EMERGENCY STOP functions are always fully functional.
Cable resistance
Flying restart operating mode
• 0: Flying restart inactive
• 1: Flying restart always active (start in setpoint direction)
• 2: Flying restart active after On, error, OFF2 (start in setpoint direction)
• 3: Flying restart active after error, OFF2 (start in setpoint direction)
• 4: Flying restart always active (start only in setpoint direction)
• 5: Flying restart active after On, error, OFF2 (start only in setpoint
direction)
• 6: Flying restart active after error, OFF2 (start only in setpoint direction)
Flying restart search current
Flying restart search speed factor
Flying restart, V/f control status
Flying restart, vector control status
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents